Siemens landis LFL1.638 240v Control Box C21280G

[LFL1.638]
£419.27

Siemens landis LFL1.638 240v Control Box C21280G

 

PLEASE NOTE LFL BASE IS SOLD SEPARATELY.

 

Gas burner controls

• for gas, oil or dual-fuel forced draft burners of medium to high capacity

• for multistage or modulating burners in intermittent operation; for safety reasons, at least one controlled shutdown must take place every 24 hours

• with checked air damper control

• flame supervision

– with UV detectors QRA...

– with ionization probe

 

- Control and supervision of forced draft burners of expanding flame and interrupted pilot construction

- For medium to high capacity

- For intermittent operation (at least one controlled shutdown every 24 hours)

- Universally applicable for multistage or modulating burners

- For use with dual-fuel burners

- For use with stationary air heaters

The difference between 01 series and 02 series is the duration of the safety time for the pilot burner of burners equipped with pilot gas valves.

For atmospheric burners of high capacity, LFL1.638 is the type to be employed

 